Let's know your need of smart energy meter.
Acrel will get in touch with you ASAP.
Optional function: communication
Temperature and humidity measuring & controlling
Panel mounted
Accuracy Temperature ±1℃ Humidity ±5%RH Auxiliary power supply AC 85-265V, DC 100-350V Consumption Auxiliary power supply Basic power consumption(≤0.8w) Relay power consumption(each channel≤0.7w) | = |
Installation: Panel mounted Dimension(L*W*H): Pannel size (L×W): 48*48mm Cutout size (L×W): 45*45mm Housing (L×W×H): 44*44*86.7mm |
Technical Parameter | Value | |
Measuring Range | Temperature | -40.0℃~99.9℃ |
Humidity | 0%RH~99%RH | |
Precision | Temperature | ±1℃ |
Humidity | ±5%RH | |
Transmitting Output | DC 4-20mA or DC 0~20mA | |
Ser range of controlling parameter | Heating for Temoerature rising | -40.0℃~40.0℃ |
Blowing for temperature decteasing | 0.0℃~99.9℃ | |
Humidity control | 20%RH~90%RH | |
Output Contact Capacity | 5A/AC250V | |
Start/stop gap | 5 | |
Communication port | RS485, MODBUS(RTU) treaty | |
Auxiliary Power | Voltage | AC/DC 85-265V |
Consumption | Basic power consumption(≤0.8w)+relay power consumption(each channel≤0.7w) | |
Insulation Resistanced | ≥100MΩ | |
Power-frequency withstand voltage | power with shell, touchable metal parts/power with other terminal group 2kV/1 min(AC.RMS) | |
Average work time without stoppage | ≥50000 houts | |
Working condition(controller) | Temperature | -20℃~+60℃ |
Humidity | ≤95%RH, without condensation and corrisive gas | |
Altitude | ≤2500m |