Measurement: 3-phase AC Voltage
Accuracy: 0.5%
Rated Voltage: 400V or 660V AC L-L (direct connect); 100V AC L-L (via PTs)
Power Supply: 85~265V AC/DC
Communication: RS485 (MODBUS-RTU)
Alarm Output: Low&High&Unbalace Alarm
Analog Output: 4~20mA DC
DI/DO Function: 2-channel DI&2-channel DO
Standard&Certificate: CE Certificates
1. Function Overview
Function | Description&Value |
Measurement | Three-phase AC Voltage |
Display | LCD display |
Communication(Optional) | RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity) Baud Rate 2400/4800/9600/19200 bps etc. |
Alarm Output(Optional) | 1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc. |
Analog Output(Optional) | DC4~20mA,( load <500Ω) (note:Shielded wire is specially selected for the above signal input and output) |
DI/DO Switching(Optional) | DI (Digital input): 2-channel dry contact digital input with built in power supply DO (Digital output): 2-channel digital output with NO relay contact. Capacity: 3A/30VDC,3A/250VAC |
2. Main Parameters
Parameter | Description&Value | |
Input | Rated Voltage | AC Voltage Input: 400V AC L-L or 660V AC L-L (via direct connetion); 100V AC L-L (via -/100V AC PTs) |
Overload | Voltage input overload:1.2 times rated value(continuous); 10 times rated value /1 second | |
Frequency | 45~65Hz | |
Power Consumption | Power consumption of each voltage input circuit is less than 0.5VA | |
Accuracy | Voltage Measuring | 0.5% |
Power Supply | Voltage Range | AC/DC 85-265V |
Power Consumption | <5VA | |
Insulation resistance | ≥ 100MΩ | |
Power frequency withstand voltage | Between power supply set of terminals and signal input,output set of terminals 2kV/1min (RMS) Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV |
3. Environment
Condition | Description&Value |
Temperature | Operation: -10℃~+55℃; Storage: -25°C ~+70°C |
Humidity | ≤95%RH, no condensation,without corrosive gas |
Altitude | ≤ 2500m |